HONEYWELL EXPERION SERIES C
IOM + IOTA Selection GuideA correct Series C spare is a matched hardware set: the I/O function belongs to the IOM, while field termination, power and redundancy details are defined by the IOTA. This guide shows what engineers and buyers should verify before ordering. |
Honeywell defines the Input Output Module (IOM) as the electronics that perform a specific I/O function; the module plugs onto an Input Output Termination Assembly (IOTA). The IOTA holds the IOM and the field-wiring connections. Similar covers do not establish interchangeability. Start with the loop function, then select the documented IOM/IOTA pair.
| Signal AI, AO, DI, DO, pulse or universal channel. |
IOM Function, channel type and HART capability. |
IOTA Termination, field power and redundancy format. |
Project Revision, system release and approved drawings. |
The suffix is as important as the family prefix. Honeywell’s Series C specification associates CC-PAIH01 with CC-TAIX01 for a non-redundant analog-input arrangement or CC-TAIX11 for a redundant arrangement. CC-PDIL01 is paired with CC-TDIL01 or CC-TDIL11, while CC-PDOB01 uses CC-TDOB01 or CC-TDOB11 for bussed 24 V DC output. Each quotation request should preserve the complete code and identify whether the installed station is simplex or redundant.
For analog loops, confirm current or voltage input, HART requirement, single-ended or differential termination, channel count and field-power arrangement. For digital circuits, verify input or output direction, nominal voltage, bussed or relay output, source/load behavior and the exact termination assembly. An analog IOTA cannot be selected only by connector appearance, and a 24 V digital family should never be substituted for a high-voltage family without documented engineering approval.
Redundancy is implemented on the appropriate IOTA and requires the documented redundant assembly, not simply a second spare IOM. HART and non-HART variants also need separate review. Before replacing or expanding an installed station, compare the current Honeywell lifecycle notice, the Experion release, Control Builder configuration, cabinet power, approved loop drawings and plant procedures. A successor model may require engineering, wiring or software changes and should not be presented as a drop-in replacement without official confirmation.
Record the IOM and IOTA labels together, including Honeywell part numbers and revision markings. Confirm the signal list, channel usage, redundancy requirement, HART devices, field-voltage details and cabinet location against the engineering database. Distinguish an exact maintenance replacement from a planned migration. This workflow applies to process plants, utilities and remote I/O cabinets.
Confirm the complete model, part number, revision, Experion release, quantity and label information before ordering. Review the related Honeywell product category; only exact product pages are linked below.
| Model | Hardware Role / Description |
|---|---|
| CC-PAIH01 | High-level analog input with HART IOM |
| CC-TAIX01 | Analog input IOTA, non-redundant |
| CC-TAIX11 | Analog input IOTA, redundant |
| CC-PAIX01 | High-level analog input without HART IOM |
| CC-TAID01 | Differential analog input IOTA, non-redundant |
| CC-TAID11 | Differential analog input IOTA, redundant |
| CC-PAIN01 | High-level analog input without HART IOM |
| CC-TAIN01 | Analog input IOTA, non-redundant |
| CC-PAOH01 | Analog output with HART IOM |
| CC-TAOX01 | Analog output IOTA, non-redundant |
| CC-TAOX11 | Analog output IOTA, redundant |
| CC-TAON01 | Analog output IOTA, non-redundant |
| CC-PDIL01 | 24 V DC digital input IOM |
| CC-TDIL01 | 24 V DC digital input IOTA, non-redundant |
| CC-TDIL11 | 24 V DC digital input IOTA, redundant |
| CC-PDIH01 | High-voltage digital input IOM |
| CC-PDOB01 | Bussed 24 V DC digital output IOM |
| CC-TDOB01 | 24 V DC bussed-output IOTA, non-redundant |
| CC-TDOB11 | 24 V DC bussed-output IOTA, redundant |
| CC-PUIO31 | 32-channel universal I/O module |
| CC-TUIO31 | Universal I/O IOTA, non-redundant |
| CC-TUIO41 | Universal I/O IOTA, redundant |
Use the complete manufacturer reference shown on the product label when requesting a quotation.
| Model Reference | Model Reference | Model Reference |
|---|---|---|
| 52400659 | VS-5FDT-1 | 2cdg110125R0011 |
| 100-02823 | 420-10E | MA3751Z.3Z MA3751Z |
| ABE7 P16T334 - EM/SS | i1010 | 7PU4020-1AJ20 |
| 1771-IAD 96220672 A01 | TA25DU 1SAZ211201R1025 | CQM1-PRO01-E |
| GE IC693APU300HRA | IMDSI02 | 3AA01318700 |
| U891RX | F2108 | AT-HDTX-IR |
| AF20AOpens | GSA-SB | C-TSDI-1624C |
| 90984/3/1 | 837-1 1002107404AA | RF-4200-01-1 |
| QIO-PCIE | cantrol-CEDIO-p 24/24/2-0 | 9150-28178-02 |
| ES5D001VST00 ES5D00ETPC00 | RKC4.221T-30/TEB | ABB DO573 1SAP231300R0000 |
| QBM2030-30 | UNC-500 | 60-2720 0160-2720 -144400-0004 |
| EC401-11 | EL900-A-N-1-A | ABB 251 204-AN |
| PM850UMG | SCS LG-003842 | FCSM082300 |
| ABB DC532 | H3C X362 5500 / 5130 HI JG544A PSR720-56AH | PXC3.E72 S55376-C100 |
| Allen Bradley 80025-523-10-R | 3286-20 | 1F83-71 2 |
| ET901-DC | PW7K1R2B/PRO42R2B | STR350 004600100 |
| MTL688 | GN50 | MTL4541AS |
| 2cdg 110 171 R0011 | RB2 BA4 | MC1490A |
| TA200DU-90 66-90A 1SAZ421201R1001 | Gent S4-720 | 3100321 |
| ABB 2CSYD0202B 2CSY290962R0202 | SCMD6400 | ABB RC/A4.2 |