HIMatrix F35 011 Product datasheet
|
Model number: |
HIMatrix F35 011 |
|
Module Type: |
Safety-Related Controller |
|
Manufacture: |
HIMA |
|
Condition: |
Brand New |
|
Range of Product: |
HIMA |
|
Lead time: |
In Stock |
|
Weight: |
0.1kg |
|
HS CODE: |
8537101190 |
|
Dimension: |
2.5x12.7x20.3cm |
|
MOQ: |
1 |
|
Product Origin: |
GERMANY |
|
System: |
DCS |
|
Discontinued on: |
active |
|
Communication Service: |
Ethernet router |
HIMatrix F35 011 Functional Description
The HIMA HIMatrix F35 011 Safety Controller is a compact safety controller certified for SIL 3 applications according to IEC 61508 and related standards. This robust module, the Safety-Related Controller HIMA HIMatrix F35 011, integrates 24 digital inputs, 8 digital outputs, 2 counters, and 8 analog inputs within a single unit, providing comprehensive I/O capabilities for complex safety functions.
Its operating temperature range of -20°C to +60°C ensures reliable performance in demanding industrial environments, making it suitable for various harsh condition applications.
A significant advantage of the HIMA HIMatrix F35 011 Safety-Related Controller is its integrated line monitoring capability for digital outputs, where analog inputs can be configured to detect short-circuits and open-circuits, achieving SIL 3 compliant diagnostics. The Controller module HIMA HIMatrix F35 011 is programmed using the SILworX engineering tool, which simplifies configuration of safety functions while maintaining the required safety integrity. This controller's versatile I/O structure allows direct connection of actuators like solenoid valves while providing comprehensive monitoring of both the field devices and supply voltage.
The HIMA HIMatrix F35 011 IN STOCK represents a complete safety solution that reduces system complexity by integrating multiple functionality types in one certified package. The combination of diverse I/O types, built-in diagnostics, and user-friendly programming establishes the module as an ideal platform for implementing safety instrumented functions in process automation, emergency shutdown systems, and other critical protection applications where reliability and diagnostic coverage are essential requirements.
If you have other request contact our team to get customized service



Call +86 18159889985 to be connected with our Manager Stella
Email to sales6@apterpower.com get your best quotation
For the quick assistance message us on WhatsApp at +86 18159889985 now!
|
HIMA |
Z1001 |
HIMA |
F7130A |
HIMA |
F3430 |
|
HIMA |
F7546 |
HIMA |
F7130 |
HIMA |
F3423 |
|
HIMA |
F3330 |
HIMA |
F7126 |
HIMA |
F3421 |
|
HIMA |
F3322 |
HIMA |
F7105A |
HIMA |
F3417A |
|
HIMA |
F3237 |
HIMA |
F6705 |
HIMA |
F3349 |
|
HIMA |
F3236 |
HIMA |
F6251 |
HIMA |
F3331 |
|
HIMA |
F3226 |
HIMA |
F6217 |
HIMA |
F3330 |
|
HIMA |
H7506 |
HIMA |
F8651E |
HIMA |
F8650X |
|
HIMA |
F7541 |
HIMA |
F8620 |
HIMA |
F8627 |
|
HIMA |
F7553 |
HIMA |
F8621 F8621/A |
HIMA |
F8641 |
Line Monitoring for Digital Outputs
The analog inputs can be used to monitor the digital outputs for short-circuits and opencircuits.
Figure 3 shows a circuitry for line monitoring (open circuits and short-circuits) that complies with SIL 3. Additionally, the S1 supply voltage is monitored via a digital input DI.
In this application, the actuator (e.g., solenoid valve) is connected to the digital output between DO and L-.
All specified electronic components must be directly attached to the clamps.
The reaction to open-circuits and short-circuits must be configured in the user program.